48-7009-E 4-23
4.2.6 How to set control types
How to set control types is described.
Constant value run mode screen
PV value (present value)
SV value (target value)
Hold MODE key pressed for 2 seconds.
Each set screen
Each setting mode
Press the ▲ key three times.
Press it, however, twice for TTM-204.
Press MODE key six times.
S04-6 Control type setting screen
* Set the control types in this screen.
* The number displayed in the screen is coincident with that listed in the control type setting table.
* Use the ▲/▼ key for the setting.
* The value is set at “1” at factory shipment.
S04-8 PID control type setting screen
Continued to the next page
* The PID control types are set in this screen.
* The number displayed in the screen is coincident with that listed in the PID control type setting table.
* Use the ▲/▼ key for the setting.
* The value is set at “1” at factory shipment.
Hold MODE key pressed for 2 seconds.
Control type setting table
PID control type setting table
Type B (overshoot suppression)
Type C (disturbance suppression)
For program run mode screen:
PV value (present value)
SV value (PRoG)
Hold MODE key pressed for 2 seconds
Setting mode is the same as that for constant
value run mode.
(To input 1 setting screen)