48-7009-E 6-52
1) State when no event has occurred
No event occurs when RUN/READY is switched over.
2) Standby state
No event occurs when RUN/READY is switched over.
3) State when an event has occurred (an event occurs when the event moves out from the standby state.)
By switching over from RUN to READY, the event turns to OFF. It goes to 2)standby state.
■ Event function 2 setting (PV abnormality)
Control mode interlocking function
Set the event function 2 (PV abnormality).
Event function 2 is a function to output signals (ON/OFF) from the outputs 1 to 7 that are assigned for the event function 2
when an abnormality is generated in the input 1.
This function is effective when the event function 2 is set to **1.
This function is useful in case of improper setting of the input 1 type, alarming for input improper wiring, disconnection or
short, or start/stop of other systems.
This function can be used when the target connection for the outputs 1 to 7 are set for the event output.
Note Take care that the event function 2 may event-output when input 1 type is being changed.
For the operation range of the event function 1 and each setting value, see section of event function 1 operation on page 6-49.
For the add-on function of the event function 2 and the control mode interlocking setting, see again section of event function 1
operation on page 6-49
Example of PV abnormal setting: In the case of PV Abnormal, No Added Function, Control Mode
Interlock Full Mode, set to “001”.