This section introduces the timer function. Timer behavior is determined by defining the following
parameters: timer function setting [tMF 1 to tMF 3], unit setting [H/M 1 to H/M 3], SV start allowable
range setting [tSV 1 to tSV 3], On delay timer [oNt 1 to oNt 3], Off delay timer [oFt 1 to oFt 3],
repetition count setting [RUN 1 to RUN 3], etc.
(Timer function setting)
SEt14
tIME1
to
SEt16
tIME3
DI 1 start (settable when an option existent)
DI 2 start (settable when an option existent)
DI 3 start (settable when an option existent)
DI 4 start (settable when an option existent)
Event 3 start (settable when an option existent)
Event 4 start (settable when an option existent)
Event 5 start (settable when an option existent)
Event 6 start (settable when an option existent)
Event 7 start (settable when an option existent)
(Unit setting)
If the SV start is set, set the temperature in C or the digit width range which a timer starts.
(SV start permissible range setting)
Thermocouple/resistance temperature detector input
0.0 to 999.9 (C)
0 to 999 (C)
Voltage/current input
0 to 9999 (digit)
• The allowable range is set in range of tSV with its center at the SV value as illustrated below.
• If tSV is set to 1.0 C, the timer becomes active when a temperature falls within the SV value 0.5
C.
Note If the ramp function is also used, tSV is attached to a target SV value.