Event function 4 (loop abnormality)
SEt05
oUt1
to
SEt11
oUt7
Setting content
Initial value
9
E1F4
to
E7F4
Function
00
*0
Nonexistent
*1
Existent
Add-on function
0*
None
1*
Hold
Set the event function 4 (loop abnormality).
Event function 4 is a function that detects output abnormalities, and that outputs signals from the event output.
This function can be used when the event function 4 is set and the target connections of the outputs 1 to 7 are set to event
outputs.
For details of the setting of the loop abnormality, see section 5.4.6 Loop abnormality function on pages 5-38 and 39.
For the setting of the loop abnormality time, see section of primary/secondary control loop abnormality time setting on pages
6-27and 40
Event polarity setting
SEt05
oUt1
to
SEt11
oUt7
Setting content
Initial value
10
E1P to E7P
0
Normal open
0
1
Normal close
Set close active or open active for the event function setting.
Close active: Event function closes when the event output is in the active state.
Open active: Event function opens when the event output is in the active state.