Secondary control sensitivity setting
SEt04
CNt
Setting content
Initial value
51
C2
Thermocouple/resistance temperature detector input
0.0 to 999.9 (C)
0 to 999 (C)
1
Voltage/current input
0 to 9999 (digit)
10
Set the secondary control sensitivity.
Sensitivity (hysteresis) of ON/OFF operation is set. For heating control, the sensitivity is set in the upper side of SV.
Secondary control off-point position
SEt04
CNt
Setting content
Initial value
52
CP2
Thermocouple/resistance temperature detector input
-999.9 to 999.9 (C)
-999 to 999 (C)
0
Voltage/current input
-9999 to 9999 (digit)
Set the secondary control off-point position.
Moving the off-point of the secondary control sensitivity results in a move of entire range of the sensitivity.
<Reverse operation>
Off-point CP2 = 0
C2
ON
OFF
PV
Low
SV
High
Off-point CP2 = positive value
CP2
C2
ON
OFF
C point
PV
Low
SV
High
Off-point CP2 = negative value
C2
CP2
ON
OFF
D point
PV
Low
SV
High
C2: Sensitivity setting
C2: Sensitivity setting
CP2: Off-point position
C point: SV + CP2
C2: Sensitivity setting
CP2: Off-point position
D point: SV - CP2