Toho-electronics TTM-339 Bedienungsanleitung Seite 25

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 32
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 24
- 25 -
5.7 Common parameter setting mode SET 9 (2)
SET09
Name
Setting content
Initial value
With the selection of [MLF = 2,3], the following 18 to 41 are selectable.
18
CM1
CT1 current value monitor
0.0 to 50.0 (A) Displays the average at MLF=2.
Displays the R.M.S at MLF=3.
19
OH01
Operation amount limiter point 1
A point is defined as a location corresponding to the number resulted from
calculation of divided values of SLL to SLH into 10 equal segments
multiplied by the point No.
0.0 to 100.0 (%)
100.0
20
OH02
Operation amount limiter point 2
21
OH03
Operation amount limiter point 3
22
OH04
Operation amount limiter point 4
23
OH05
Operation amount limiter point 5
24
OH06
Operation amount limiter point 6
25
OH07
Operation amount limiter point 7
26
OH08
Operation amount limiter point 8
27
OH09
Operation amount limiter point 9
28
OH10
Operation amount limiter point 10
29
OH11
Operation amount limiter point 11
30
AH01
Current value limiter point 1
Upper current limit at the operation amount limiter point
0.0 to 30.0 (A)
30.0
31
AH02
Current value limiter point 2
32
AH03
Current value limiter point 3
33
AH04
Current value limiter point 4
34
AH05
Current value limiter point 5
35
AH06
Current value limiter point 6
36
AH07
Current value limiter point 7
37
AH08
Current value limiter point 8
38
AH09
Current value limiter point 9
39
AH10
Current value limiter point 10
40
AH11
Current value limiter point 11
41
AHC
Current value limiter sensitivity
0.1 to 30.0 (A)
0.2
42 and 43 are always effective; 44 and 45 are selectable when [CNT = 3].
42
OU1
Primary control operation amount
increase rate
0.0 to 549.9 (%): 0.0% indicates the function turned off.
0.0
43
OUTM1
Primary control operation amount
increase time
0 to 3600 (second): 0 indicates no function.
0
44
OU2
Secondary control operation
amount increase rate
0.0 to 549.9 (%): 0.0% indicates the function turned off.
0.0
45
OUTM2
Secondary control operation
amount increase time
0 to 3600 (second): 0 indicates no function.
0